Project Description

CIBRE-30B BLUE Brochure
Brochure_English

CIBRE-30B BLUE, 3 Contacts Circuit Breaker Analyser is designed by advanced engineering technology to test contact timings of circuit-breakers. CIBRE-30B BLUE has a fast, easy and accurate measurement features by its user-friendly software. CIBRE-30B BLUE is a battery-powered device, which allows users to perform tests even without power supply during on-field tests.

FEATURES

  • Contact Timing (O, C, O-C, C-O and O-C-O)
  • Motion Tests (Transducer Speed, Stroke, Bounce)
  • 3 Dry Contact Inputs
  • Timing Accuracy: 0.05% rdg ± 0.1 ms
  • Timing Windows: 1s, 10s & 20s
  • Contact Detection Range: Closed ≤20 Ω & Open ≥5000
  • Battery Powered
  • Bluetooth Communication
  • PC Software
  • 2.28” Built-in Printer
  • 7” TFT Touch Colour Display
  • Light-weight and Portable
  • Protection Class IP67 (case closed)

DETAILS

Why test circuit breakers?

It is very important to test circuit breakers regularly. Contact Timing Tests and Motion tests are performed to determine the optimal performance of the breakers. The testing can determine improper breaker operations in case of system fault and to improve system reliability.

Contact Timing Tests

Contact timing tests are performed to compare the breakers’ main & resistor contact performance against the manufactures specifications. The breakers OPEN, CLOSE, OPEN-CLOSE, CLOSE-OPEN & OPEN-CLOSE-OPEN operations are timed in milliseconds (ms) and cycles and then compared with the manufacturers’ specification to determine the performance of the circuit breaker.

Motion Tests

CIBRE-30B BLUE can use to perform motion tests such as Transducer Speed, Stroke and Bounce. Slower transducer speed can reduce the breaking capacity of the main contact while faster speed can cause mechanical damage to the damping components and cause excessive vibration. So it is necessary to test the transducer speed to compare it with manufacture’s specifications.

CIBRE-30B BLUE features with a 7-inch large colour touch display, which is visible under both bright sunlight as well as dim light conditions. With the HighTest Data Management Platform (DMP Software), users can analyse and manage measurement results on PCs. Operators can easily print the measurement results with the 2.28-inch built-in printer of CIBRE-30B BLUE. The results can also save to a USB flash drive or to the device’s internal memory.

Multi-language capability and user-friendly operation menu make it easy to control CIBRE-30B BLUE. CIBRE-30B BLUE is a light-weight, compact and rugged device with the protection of IP67 (case closed) which makes it perfect for the field test.

TECHNICAL SPECIFICATIONS

Measurement ParametersContact Timing (O, C, O-C, C-O & O-C-O), Motion Tests (Transducer Speed, Stroke, Bounce)
Dry Contact Inputs3 dry input channels (each detects main) and insertion resistor contacts
Timing Windows1s, 10s, 20s
Timing Resolution1 s duration10 s duration20 s duration
± 50 µs± 500 µs± 1 ms
Timing Accuracy0.05% rdg ± 0.1 ms
Dry contact channel protectionFuses and Diodes protection, All contacts grounded until Test
Contact detection rangeClosed≤20 Ω
Open≥5000 Ω
Resistor detection range20Ω – 5000Ω
Trigger input voltage24 – 300 V DC or ACpeak
Dry contact input protectionDiode Protection/ FSD
Breaker OperationsOPEN, CLOSE, OPEN-CLOSE, CLOSE-OPEN, OPEN-CLOSE-OPEN
Voltage sensing input rangeV1 (Analogue Input)V2 (Presence/Absence Detector)
0 – 250 V DC or ACpeak24 – 300 V DC or  ACpeak
Breaker Initiate Capacity20 A, 300 V DC or ACpeak
Digital Travel Transducer Input5V/12Vdc TTL
Initiate current reading range0 – 20A DC, 5 kHz
Input Power100-240 V,  47/63 Hz
Built-in BatteryYes, 14.4 V 6.9 Ah
Display7-inch Colour Touch Display
MemoryUp to 200 records
printer2.28 inches Built-in Printer
PC SoftwareDMP Software (Windows 10)
Dimensions16.9″ x 12.9″ x 9.3” (429 mm x 328 mm x 236 mm)
Weight8.2 kg with battery
CommunicationUSB 2.0/1.1 Standard-A, USB 2.0/1.1 Standard-B,  Bluetooth
Working Temperature-10 °C to + 60 °C
Humidity90% RH non-condensing
Protection ClassIP67 (case closed)

*Specifications are valid at/under 25 °C temperature. *Contents subject to change without notice.